Condensate draining methods

Home

Methods of Draining Condensate

There are four methods to drain condensate. They are manual, level-operated mechanical traps, electrically operated solenoid valves and zero air loss traps with reservoirs.

In order to discharge condensate utilizing the manual method, operators will physically open the valves. The drawback with this procedure is that manual valves are quite often left open to drain the condensate from moisture separators, intercoolers, refrigerated dryers and filters. When this occurs, compressed air is able to continuously leak into the air.

With the level-operated mechanical traps, such as the float-type traps, air cannot be wasted when operated correctly. However, these traps often need a substantial amount of maintenance. They may also be susceptible to blockage from sediment remaining in the condensate. Not as much maintenance is needed with inverted bucket traps, although they may waste compressed air if the condensate rate is not sufficient to preserve the level of liquid (prime) contained in the trap.

A timing device is contained on the solenoid-operated drain valve that may be set to open for only a specified period of time, as well as at preset variable intervals. However, there are a couple of disadvantages with these valve. There may not be enough time for adequate drainage of accrued condensate during the period of time in which the valve is open. Also, if there is little or no condensate, the valve will function anyway, and as a result there will be a loss of valuable compressed air. Since contaminants may block the inlet and discharge ports of the level-operated and electrically operated solenoid valves, they should contain strainers in order to reduce those contaminants.

Programmable timers may contain motorized ball valves which are quite dependable, although these valves can be more wasteful than the other types because the period of time that the valve is open is actually dependent on the valve actuator and it is not adjustable.

There are different types of zero air-loss traps with reservoirs. an electric solenoid or ball valve is operated by a float or level sensor. This type preserves the condensate level in the reservoir below the high-level point. A pneumatic signal becomes activated by a float which transmits the signal to an air cylinder in order to open a ball valve through a link to force out the condensate in the reservoir to the low-level point. The reservoir must be drained frequently so that the contaminants do not accumulate, as that could harm the mechanisms of the traps. Heated drains should be installed when there is the potential for freezing. A manual drain valve should not be cracked open because it will cause costly compressed air to be wasted.

Before the contaminated condensate can be discharged to a sewer system, the lubricant should be removed. Contact your local sewage authority to find out the allowable levels of contamination.
 

 

 Resource links Air compressors guide   Tools Tool Related

usingaircompressors.com

 

About air compressors

Terms and Disclaimer

Tool Related

 

Sample a few of the articles below about air compressors:

Industrial Air Compressors

Natural Gas-Driven Air compressors

air compressor types

Natural Gas benefits

Understanding the language of air compressors

Copyright usingaircompressors.com. All rights reserved world wide.
All trademarks and service marks are property of their particular owners.